LUTZE DRIVEFLEX® XLPE PVC VFD Cable, A216

Shielded with RHW-2 XLPE insulation

1000V Flexible VFD Servo Cable, WTTC, 600V TC-ER

LUTZE DRIVEFLEX ® A216 VFD cable is your cable solution for power connections between electric motors and Variable Frequency Drives (VFD). The first cable introduced under the DRIVEFLEX ® family, the A216 incorporates RHW-2 XLPE insulation, making it ideal for applications with voltage spikes and long cable runs. DRIVEFLEX ® meets the unique electrical challenges in VFD and Servo applications as well as NFPA 79 2018 article 4.4.2.8

Shielded construction:

Configuration: 3 Power conductors + GND

Conductor: class K stranded tinned copper

Insulation: XLPE type RHW-2

Color code: black w/ white #s, green/yellow ground

Shielding: foil tape, tinned copper braid and drain wire

Jacket: oil resistant PVC, black

Voltage

600V 90C UL TC-ER-JP

1000V 90C Flexible VFD Servo

Cable, 1000V 105C AWM

1000V WTTC

Temperature

-40°C – +105°C static

Bending Radius

6 x cable OD

Oil Resistance

Oil Res II

  • UL Type Flexible Motor Supply Cable

  • UL Type Flexible VFD Servo Cable

  • TC-ER-JP

  • WTTC

  • DP-1

  • Meets NEC 336, 392 Class I & II, Div. 2 and Class I Zone 2 per NEC 501, 502, 505

  • AWM 20886

  • Submersible Pump (≥AWG14)

  • c(UL) TC, CIC FT4

  • UL 1277

  • P-07-KA130021-MSHA

  • RoHS

  • REACH

  • Shielded multi-conductor cable for VFD and Motor applications to connect power from drives to motors

  • Cable design for harsh industrial environments and operating conditions with high noise levels

  • Thermoset XLPE insulation offering superior overload and short-circuit temperature

  • Increased wall thickness insulation type RHW-2, offering lower capacitance and higher impedance making it ideal for applications with high voltage spikes and long cable runs

  • Compliant with NFPA 79 for wiring of industrial machinery

  • TC-ER-JP for use with cable trays without conduit, which can reduce material and labor costs

  • WTTC – wind turbine tray cable rating for use in wind power generation

  • Dry, damp or wet conditions

  • Flexible XLPE conductor design

  • Non-wicking fillers

  • Effective dual layer shield for EMC compliance

  • Specially formulated jacket for oil resistance and easy strip

  • Crush impact resistant

  • Gas/vapor-tight sheath per UL 1277

  • Low capacitance cable

  • Sunlight resistant

  • Flame retardant

  • Direct burial

  • Talc and Silicone free

Part Number Manufacturer Description AWG # of Cond. Nom OD (in)

16AWG

A2161604 LUTZE LUTZE DRIVEFLEX® XLPE RHW-2 AWG16/4C UL/TC/VFD/WTTC/CE 1000V BLACK 16 4 0.488

14AWG

A2161404 LUTZE LUTZE DRIVEFLEX® XLPE RHW-2 AWG14/4C UL/TC/VFD/WTTC/CE 1000V BLACK 14 4 0.559

12AWG

A2161204 LUTZE LUTZE DRIVEFLEX® XLPE RHW-2 AWG12/4C UL/TC/VFD/WTTC/CE 1000V BLACK 12 4 0.614

10AWG

A2161004 LUTZE LUTZE DRIVEFLEX® XLPE RHW-2 AWG10/4C UL/TC/VFD/WTTC/CE 1000V BLACK 10 4 0.701

8AWG

A2160804 LUTZE LUTZE DRIVEFLEX® XLPE RHW-2 AWG8/4C UL/TC/VFD/WTTC/CE 1000V BLACK 8 4 0.925

6AWG

A2160604 LUTZE LUTZE DRIVEFLEX® XLPE RHW-2 AWG6/4C UL/TC/VFD/WTTC/CE 1000V BLACK 6 4 1.012

4AWG

A2160404 LUTZE LUTZE DRIVEFLEX® XLPE RHW-2 AWG4/4C UL/TC/VFD/WTTC/CE 1000V BLACK 4 4 1.154

2AWG

A2160204 LUTZE LUTZE DRIVEFLEX® XLPE RHW-2 AWG2/4C UL/TC/VFD/WTTC/CE 1000V BLACK 2 4 1.346

Customer Service

In a lean distribution model, everything is done with the customer in mind. There is nothing lean about our customer service, paramount here at Right Hand Industrial. From general questions and quotations through delivery, we are your trusted "right hand" for quality electrical wire and cable, connectors, automation components and cable management solutions for industrial applications.